LCD Passive Repeater Panel FL-4000/RP
(AGNI)
LCD STATUS INDICATOR
MICRO - CONTROLLER BASED FOR BETTER RELIABILITY AND PERFORMANCE
SURFACE MOUNTING INTALLATION
Technical Specification
• LPCB
• EN54-2:1997 + A1:2006
• EN54-4:1997 + A1:2002 + A2:2006
Control Panel
Input Voltage
• 240VAC ±10% / -15%, 50/60Hz
Input Current Consumption
• 1A
PSU Output to CIE
• 24.5 to 28.5VDC
Batteries
• 2 × 12V / 24Ah
Memory (Non-Volatile)
• 1000 Fire Events
• 10,000 General Events
Zones
• 3000 Programmable
Groups
• 3000 Programmable
Programmable Relays
• 4 Circuits (Normally Open / Close)
Programmable Input
• 1 Circuit (Power Limited 24VDC – For Future Use)
Programmable Auxiliary Power
• 19 to 28VDC (Current Limited)
Fixed Outputs (FPE / Sounder)
• 2 Circuits (18 to 28VDC, Current Limited)
Indicators
• 24 LED Status Indicators
• 160 Zone Indicators
Display
• 7" TFT Touch Screen
Keypad
• 5 Brigade Buttons with Programming Keypad
Physical
Material / Color
• Flat Sheet Metal
• Outer Glass Door
• Orange Stripe
Dimensions (L × W × H)
• 530 × 490 × 135 mm
Weight
• 16.70 kg (4 Loop Panel)
Humidity
• 0 to 95% Relative Humidity
• Non-Condensing
Loop Specifications
Protocol / Addressing
• Agni Addressing
• Address Range: 1 to 254
Number of Loops
• 4 Loops
• 254 Devices per Loop
Protection
• Built-in 4kV Surge Protection
Power Rating
• 16 to 24VDC / 500mA
Cable Requirement
• Maximum Cable Length: 1.2 km
• 2 × 1.5mm² Solid Core Fire Resistance Cable
Networking and Interfaces
Panel to Panel Communication
• CAN Bus (Loop)
Number of Panels
• Up to 512 Panels
Interface Ports
• USB
• RS485 Serial
• RS232 Serial
• Ethernet
Certification
• EN54-2:1997 + A1:2006 Certified
• EN54-4:1997 + A1:2002 + A2:2006 Certified
Approval
• LPCB Approved
Advanced Microprocessor Technology
• Using advanced microprocessor technology with large memory capacity
User Interface
• Enhanced user interface combining LCD Touch Screen and keypad access
Visual Algorithm
• Supports real-time visual algorithm
False Alarm Prevention
• Enhanced false alarm prevention
Programming
• Keypad and PC programming
Communication Interface
• Built-in multiple interface protocols such as USB, Ethernet, CAN Bus, Serial and RS485 (Available only in FL-4004 Panel)
Loop Powered Devices
• Supports loop-powered devices for extra savings on cable cost
Printer & LED Indicators
• Built-in Printer and 160 LED Zone Indicators
Commissioning Advantages and Capacity
Auto Enrolling
• Auto enrolling of devices
Loop Mapping
• Loop mapping with color coding status
Device Monitoring
• Monitors device mismatch and dual address conflict
Command Builder
• Creates fire event scenarios using Command Builder
Loop Protection
• Loop protection against power surge
Sounder Programming
• One-man test with ON/OFF sounder programming protection
Network Application
• Supports up to 4 loops in network application with built-in 4-in-1 communication card
Devices Per Loop
• Supports 254 devices per loop
Standalone Capacity
• Maximum 6 loops in standalone mode (1,524 devices)
Network Capacity
• Supports network up to 512 nodes
Programmable Capacity
• Fully programmable system
Zones
• Up to 3000 programmable zones
Sounder Groups
• 1–1000 Sounder Groups
Module Groups
• 1001–2000 Module Groups
LED Zone Indicators
• Built-in 160 LED Zone Indicators